HUCEEN SM1232 AQ4 x 14 Bits

Description

General Description:

  • Model No: SM1232 AQ4 x 14 Bits
  • Article No: H7 232-4HD32-0XB0
  • Description: Analog output module with 4 outputs, each providing 14-bit resolution.
  • Conventional Norm: N/A (Typically implies conformance to industrial standards for communication and performance)

Physical Dimensions:

  • Dimensions (WxHxD): 45 x 100 x 75 mm

Electrical Characteristics:

  • Power Consumption:
    • 1.5W (at typical operation)
  • Current Consumption:
    • 80 mA (via SM bus)
    • 45 mA (via 24V DC, no load)

Analog Output:

  • Number of Outputs: 4 analog outputs
  • Output Types:
    • Voltage or Current
  • Output Ranges:
    • Current Output:
      • 0 – 20 mA or 4 – 20 mA
    • Voltage Output:
      • ±10 V
  • Data Word Format:
    • Voltage Mode: -27648 to 27648
    • Current Mode: 0 to 27648
  • Resolution:
    • Voltage Mode: 14 bits (standard resolution for voltage output)
    • Current Mode: 13 bits (slightly lower resolution for current output)
  • Maximum Voltage Resistance: ±60 V (can withstand voltage up to ±60V without damage)
  • Isolation (Field Side and Logic Side): 500 VAC (electrical isolation for safety and noise immunity)

Performance Characteristics:

  • Precision:
    • Full range precision at 25°C: ±0.3%
    • Temperature range (0–55°C): ±0.6%
  • Stability Time:
    • Voltage Mode:
      • 300 µs for resistive loads (R)
      • 750 µs with a 1 µF capacitor
    • Current Mode:
      • 600 µs for 1 mH load
      • 2 ms for 10 mH load
  • Load Impedance:
    • Voltage Mode: ≥ 1000 Ω
    • Current Mode: ≤ 600 Ω

Operational Features:

  • Output Status in STOP Mode:
    • Outputs hold the previous value or return to a replacement value (default is 0).
  • Diagnosis and Fault Monitoring:
    • Overflow/Underflow Detection: Supported (for both voltage and current modes)
    • Voltage Mode Short Circuit to Ground Detection: Supported
    • Current Mode Circuit Break Detection: Supported