HUCEEN EM DR16 Digital input/output module

Description

8-digital input/ 8-digital output, relay

General Overview

  • Model: EM DR16
  • Article No.: E 288-2DR16-0AA1
  • Description: 8 Digital Inputs / 8 Digital Outputs (Relay Type)

Physical Specifications

  • Dimensions (WxHxD): 47 x 100 x 81 mm
  • Power Consumption: 5.5W
  • Current Consumption (SM Bus): 145mA
  • Current Consumption (24V DC):
    • Input Points: 4mA per input point
    • Relay Coils: 11mA per relay coil

Digital Input Specifications

  • Number of Inputs: 8
  • Input Type: PNP/NPN (IEC Type 1 Sinking)
  • Surge Voltage (Maximum): 35VDC (lasting 0.5s)
  • Logic 1 Signal (Minimum): 15VDC
  • Logic 0 Signal (Maximum): 5VDC
  • Optical Isolation:
    • Field Side and Logic Side: 500V AC (lasting 1 minute)
  • Isolation Group: 2
  • Filter Time: Selectable (0.2ms, 0.4ms, 0.8ms, 1.6ms, 3.2ms, 6.4ms, 12.8ms) — up to 4 inputs form one group
  • Maximum Number of Inputs Connected Simultaneously: 8
  • Cable Length:
    • Shielded Cable: 500 meters
    • Unshielded Cable: 150 meters

Digital Output Specifications

  • Number of Outputs: 8
  • Output Type: Relay
  • Voltage Range: 5-30V DC or 5-250V AC
  • Surge Voltage (Maximum): 7A during power-on
  • Rated Current per Output Point (Maximum): 2.0A
  • Switching Delay:
    • Disconnection to Connection: Maximum 50µs
    • Connection to Disconnection: Maximum 200µs
  • Optical Isolation:
    • Field Side and Logic Side: 1500V AC (lasting 1 minute for coils and contacts); none for coils and logic
  • Isolation Group: 2
  • Output Status in STOP Mode: Previous value or replacement value (default is 0)

Connectivity & Cable

  • Maximum Number of Outputs Connected Simultaneously: 8
  • Mounting Orientation:
    • Horizontal: 55°
    • Vertical: 45°
  • Cable Length:
    • Shielded Cable: 500 meters
    • Unshielded Cable: 150 meters