Description

4-channel thermocouple module

Model and Article Information

  • Model Number: EM AT04
  • Article Number: E 288-3AT04-0AA1
  • Description4-channel thermocouple module designed for precise temperature measurements using thermocouples.

Physical and Power Specifications

  • Dimensions (WxHxD): 47 mm × 100 mm × 81 mm
  • Power Consumption: 1.5 W
  • Current Consumption:
    • SM bus: 120 mA
    • 24V DC: 40 mA

Analog Input Specifications

  • Number of Inputs: 4 channels for thermocouple connections
  • Measuring PrincipleSigma-Delta (provides high-precision conversion from analog to digital)
  • Resolution:
    • Temperature: 0.1°C / 0.1°F
    • Voltage: 15 bits + symbol bits (for voltage measurement, providing high resolution)
  • Max. Voltage Resistance: ±35V (protects against high-voltage spikes)
  • Cold End Temperature Error: ±1.5°C (temperature compensation for the cold junction, typical in thermocouple measurements)

Isolation and Protection

  • Isolation:
    • Field side and logic side: 500V AC
    • Field side and 24V DC side: 500V AC
    • 24V DC side and logic side: 500V AC
  • Channel-to-Channel Isolation: Supported (each channel is electrically isolated for improved noise immunity and reduced cross-talk)
  • Common Mode Rejection: >120 dB at 120V AC (provides excellent noise rejection, especially in industrial environments with electrical noise)
  • Repeatability: ±0.05% FS (Full Scale) for consistent and stable readings

Cable and Sensor Specifications

  • Cable Loop Resistance (Max): 100Ω (important for ensuring signal integrity in the sensor wiring)
  • Cable Length: Up to 100 meters with shielded twisted pair cable (providing long-distance measurement capabilities while minimizing interference)

Diagnostic Features

  • Diagnosis Capabilities:
    • Overflow/underflow detection
    • Circuit break detection
    • 24V DC low voltage detection

Frequency Rejection and Filter Settings

  • Rejection Frequency Selection: The module supports different frequency rejection settings to filter out electrical noise:
    • 400 Hz (2.5 ms integration time)
    • 60 Hz (16.6 ms integration time)
    • 50 Hz (20 ms integration time)
    • 10 Hz (100 ms integration time)
  • Note:
    • When 400 Hz inhibition is selected, the integration time is reduced to 10 ms, maintaining the module’s resolution and accuracy, while suppressing noise at 100 Hz and 200 Hz frequencies.