HUCEEN EM AR02 Thermocouple module

Description

2-channel RTD module, resolution 16 bits

Model and Article Information

  • Model Number: EM AR02
  • Article Number: E 288-3AR02-0AA1
  • Description: 2-channel RTD module with a 16-bit resolution for precise temperature measurement.

Physical and Power Specifications

  • Dimensions (WxHxD): 47 mm × 100 mm × 81 mm
  • Power Consumption: 1.5 W
  • Current Consumption:
    • SM bus: 120 mA
    • 24V DC: 40 mA

Analog Input Specifications

  • Number of Inputs: 2
  • Measuring PrincipleSigma-Delta (high-precision conversion method)
  • Resolution:
    • Temperature: 0.1°C / 0.1°F
    • Voltage: 15 bits + symbol bits (providing high precision for voltage measurements)
  • Max. Voltage Resistance: ±35V (ensuring protection against voltage spikes)
  • Max Power Consumption of Sensor: 0.5 mW

Isolation and Protection

  • Isolation:
    • Field side and logic side: 500V AC
    • Field side and 24V DC side: 500V AC
    • 24V DC side and logic side: 500V AC
    • Channel to channel isolation: None specified (common grounding for channels)
  • Common Mode Rejection: >120 dB (excellent at rejecting noise from common-mode sources)
  • Repeatability: ±0.05% FS (Full Scale)

Cable and Sensor Specifications

  • Cable Loop Resistance (Max):
    • 20Ω for standard RTD (Cu10), with a maximum of 2.7Ω for special configurations.
  • Cable Length: Can handle up to 100 meters with shielded twisted pair cable, ensuring accurate measurements even over long distances.

Diagnosis and Error Handling

  • Diagnosis Features:
    • Overflow/underflow detection
    • Circuit break detection
    • 24V DC low voltage warning (ensures proper system operation by notifying of power issues)

Frequency Rejection and Filter Selection

  • Rejection Frequency Selection:
    • 400 Hz (2.5 ms integration time)
    • 60 Hz (16.6 ms integration time)
    • 50 Hz (20 ms integration time)
    • 10 Hz (100 ms integration time)
  • Note:
    • When selecting the 400 Hz filter, the module maintains resolution and accuracy, while also suppressing noise at 100 Hz and 200 Hz frequencies.