HUCEEN E5 200smart CPU SR40 AC/DC/RLY

Description

E5 200Smart CPU Basic Edition,CPU SR40 Relay,24DI/16DO,1*RJ45,1*RS485, Expandable to 6IO

General Description

  • Model: Basic Edition CPU SR40, Relay
  • Article No.: E5 288-1SR40-0AA1
  • Norm: Conventional

Physical Dimensions

  • Size: 125 x 100 x 81 mm
  • Power Consumption: 23W
  • Available Current (SM Bus): Max 1400mA
  • Available Current (24V DC): Max 300mA

Memory & Data

  • Program Memory: 24 KB
  • Data Memory: 16 KB
  • Retentive Memory: 10 KB
  • Data Preservation: Permanent

I/O Configuration

  • Built-in Digital I/O:
    • Inputs: 24 channels
    • Outputs: 16 channels
  • Analog I/O:
    • Process Image Size: 256-bit input, 256-bit output
    • Analog Image: 56 words input (AI), 56 words output (AQ)

Expansion

  • Modules Supported: Up to 6 expansion modules
  • High-Speed Counters:
    • 4 total
    • 50 kHz (HSC0-3) for single-phase
    • 30 kHz (HSC0) for quadrature-phase
  • Pulse Output: Not available
  • Timers:
    • Non-holding: 192
    • Holding: 64
  • Counters: 256
  • Bit Memory (M): 256 bits
  • Cycle Interrupts: 2 (T32 and T96 with 1ms resolution)
  • Interrupt Edges: 4 up, 4 down
  • Real-Time Clock: 7 days (at 25°C minimum of 6 days)
  • Memory Card Support: Yes
  • Signal Expansion Board: Supported

Performance

  • Boolean Processing Time: 0.35 µs/instruction
  • Moving Word Operations: 1.2 µs/instruction
  • Floating Point Operations: 1.7 µs/instruction

Communication Ports

  • Ethernet: 1 port (10/100 Mbps)
  • Serial Ports:
    • 1 Body Serial (DB9-RS485)
    • 1 DB Board Serial (CM01-RS485-RS232)
  • HMI Connections:
    • 5 Ethernet connections
    • 4 serial connections
  • Programming (PG) Connections: 1 connection
  • Ethernet Communication:
    • PUT/GET: 5 connections shared
    • Open Type Communication: 5 connections shared
  • Data Transmission Rates:
    • Ethernet: 10/100 Mb/s
    • RS485: 9600, 19200, 187500 b/s
    • RS485 Free Port: 1200 to 115200 b/s

Isolation

  • Ethernet: Transformer isolation (1500V DC)
  • RS485: None

Cable Type

  • Ethernet: CAT5e shielded cable
  • RS485: PROFIBUS network cable

Power Supply

  • Input Voltage: 85-264V AC/DC
  • Input Current (CPU only):
    • 130mA (120V AC, no sensor power)
    • 250mA (120V AC, with sensor power)
    • 80mA (240V AC, no sensor power)
    • 150mA (240V AC, with sensor power)
  • Input Current (CPU + accessories):
    • 130mA (120V AC)
    • 190mA (240V AC)
  • Inrush Current: 16.3A at 264V DC
  • Sensor Voltage: 20.4-28.8V DC
  • Isolation:
    • Input to Logic: 1500V AC for 1 min
    • Sensor to Logic: Not isolated

Digital Inputs

  • Number of Inputs: 24 channels
  • Input Type: Sinking/Sourcing (IEC type 1 sinking)
  • Max Continuous Voltage: 30V DC
  • Surge Voltage: Max 35V DC (0.5s)
  • Logic 1 Signal: 15V DC (2.5mA)
  • Logic 0 Signal: 5V DC (1mA)
  • Optical Isolation: 500V AC (1 min)

Digital Outputs

  • Number of Outputs: 16 channels
  • Output Type: Relay, dry contact
  • Voltage Range: 5-30V DC or 5-250V AC
  • Surge Current (Max): 7A at power-on
  • Rated Current per Point (Max): 2.0A
  • Switching Frequency (Max): Not recommended
  • Turn-on/Turn-off Delay: Up to 10ms
  • Optical Isolation: 500V AC (1 min)
  • Contact Lifetime:
    • Non-loaded: 10 million cycles
    • Rated Load: 10,000 cycles