HUCEEN SM1234 AI4 x 13 Bits & AQ2 x 14 Bits

Description

General Information:

  • Model Number: SM1234 AI4 x 13 Bits & AQ2 x 14 Bits
  • Article Number: H7 234-4HE32-0XB0
  • Description: Analog input & output module with 4 analog inputs and 2 analog outputs. It supports 13-bit resolution for inputs and 14-bit resolution for outputs.
  • Dimensions (WxHxD): 45 x 100 x 75 mm
  • Power Consumption: 2W
  • Current Consumption (SM bus): 80 mA
  • Current Consumption (24V DC): 60 mA (no load)

Analog Inputs (AI4):

  • Number of Inputs: 4
  • Input Type: Voltage or current (differential) — 2 can be selected as a group.
  • Input Range:
    • Voltage: ±10 V, ±5 V, ±2.5 V
    • Current: 0-20 mA or 4-20 mA
  • Full-Scale Range (Data Word): -27,648 to 27,648
  • Overshoot/Undershoot Range (Data Word):
    • Voltage: 32,511 to 27,649 / -27,649 to -32,512
    • Current: 32,511 to 27,649 / 0 to -4,864
  • Overflow/Underflow (Data Word):
    • Voltage: 32,767 to 32,512 / -32,513 to -32,768
    • Current: 32,767 to 32,512 / -4,865 to -32,768
  • Resolution: 12 bits + signal bits
  • Max Voltage/Current Resistance:
    • Voltage: ±60 V
    • Current: ±40 mA
  • Precision (25°C / 0-55°C): Full range ±0.1% / ±0.2%
  • Analog to Digital Conversion Time: 625 μs (400 Hz inhibited)
  • Working Signal Range: Common mode voltage must be between -12V and +12V.
  • Common Mode Rejection: 40 dB, DC to 60 Hz

Analog Outputs (AQ2):

  • Number of Outputs: 2
  • Output Type: Voltage or current
  • Output Range:
    • Voltage: ±10 V
    • Current: 0-20 mA or 4-20 mA
  • Data Word Format:
    • Voltage: -27,648 to 27,648
    • Current: 0 to 27,648
  • Resolution:
    • Voltage mode: 14 bits
    • Current mode: 13 bits
  • Max Operating Resistance: ±60 V
  • Isolation (Field Side and Logic Side): 500 VAC
  • Precision (25°C / 0-55°C): Full range ±0.3% / ±0.6%
  • Stability Time:
    • Voltage: 300 μs (resistor), 750 μs (1 μF capacitor)
    • Current: 600 μs (1 mH), 2 ms (10 mH)
  • Load Impedance:
    • Voltage: ≥ 1000 Ω
    • Current: ≤ 600 Ω
  • Output Status in STOP Mode: Previous value or replacement value (default is 0)

Diagnostic Features:

  • Overflow/Underflow: Supported
  • Short Circuit (Voltage Mode): Support for short circuit to ground
  • Circuit Break (Current Mode): Support for circuit break mode