HUCEEN EM AR04 Thermocouple module

Description

4-channel RTD module, resolution 16 bits

Model and Article Information

  • Model Number: EM AR04
  • Article Number: E 288-3AR04-0AA1
  • Description: 4-channel RTD module with 16-bit resolution for accurate temperature sensing and measurement.

Physical and Power Specifications

  • Dimensions (WxHxD): 47 mm × 100 mm × 81 mm
  • Power Consumption: 1.5 W
  • Current Consumption:
    • SM bus: 120 mA
    • 24V DC: 40 mA

Analog Input Specifications

  • Number of Inputs: 4 (for multiple temperature measurements)
  • Measuring PrincipleSigma-Delta (provides high accuracy in analog-to-digital conversion)
  • Resolution:
    • Temperature: 0.1°C / 0.1°F
    • Voltage: 15 bits + symbol bits (providing high precision for voltage measurements)
  • Max. Voltage Resistance: ±35V (protects against voltage spikes or surges)
  • Max Power Consumption of Sensor: 0.5 mW

Isolation and Protection

  • Isolation:
    • Field side and logic side: 500V AC
    • Field side and 24V DC side: 500V AC
    • 24V DC side and logic side: 500V AC
  • Channel to Channel Isolation: None (the channels are not isolated from each other)
  • Common Mode Rejection: >120 dB (excellent noise rejection capability)
  • Repeatability: ±0.05% FS (Full Scale)

Cable and Sensor Specifications

  • Cable Loop Resistance (Max):
    • 20Ω for standard RTD (Cu10), with a maximum of 2.7Ω for special configurations.
  • Cable Length: Up to 100 meters with shielded twisted pair cable, ensuring accurate temperature measurement over long distances.

Diagnostic Features

  • Diagnosis Capabilities:
    • Overflow/underflow detection
    • Circuit break detection
    • 24V DC low voltage detection
  • Cable Length and Shielding: Supports up to 100 meters with shielded twisted pair cables, enhancing noise immunity and signal integrity over longer distances.

Frequency Rejection and Filter Settings

  • Rejection Frequency Selection: This feature allows users to select the filter for different frequencies, ensuring optimal performance in environments with electrical noise. Options include:
    • 400 Hz (2.5 ms integration time)
    • 60 Hz (16.6 ms integration time)
    • 50 Hz (20 ms integration time)
    • 10 Hz (100 ms integration time)
  • Note: When selecting the 400 Hz filter, the integration time is reduced to 10 ms, ensuring both accuracy and effective noise suppression at 100 Hz and 200 Hz frequencies.