HUCEEN CPU SR60 AC/DC/RLY

Description

 

E7 200Smart CPU Standard Edition,CPU SR60 Relay,36DI/24DO,1*RJ45,2*RS485, Expandable to 6IO

General Overview

  • Model Number: SR60 AC/DC/RLY
  • Article Number: E7 288-1SR60-0AA1
  • Description: Standard CPU SR60 with relay outputs, suitable for both AC/DC control applications.
  • Dimensions (WxHxD): 175 mm × 100 mm × 81 mm
  • Power Consumption: 25W

Electrical Specifications

  • Available Current:
    • SM Bus: Max. 1400mA
    • 24V DC: Max. 300mA
  • Input Voltage: 85V – 264V DC (AC compatible)
  • Input Current (CPU only):
    • 130mA at 120V AC (without 300mA power supply for sensors)
    • 250mA at 120V AC (with 300mA power supply for sensors)
    • 80mA at 240V AC (without 300mA power supply for sensors)
    • 150mA at 240V AC (with 300mA power supply for sensors)
  • Input Current (Includes CPU + Expansion Modules):
    • 130mA at 120V AC
    • 190mA at 240V AC
  • Inrush Current (Max): 16.3A at 264V DC
  • Sensor Voltage: 20.4V – 28.8V DC
  • Isolation:
    • Input to Logic: 1500VAC (lasting 1 minute)
    • Sensor to Logic: Not isolated

Memory and Data

  • Program Memory: 30 KB
  • Data Memory: 20 KB
  • Retentive Memory: 10 KB (permanent data preservation)
  • Bit Memory (M): 256 bits
  • Cycle Interrupts: 2 (T32 and T96) with a 1ms resolution
  • Counters: 256
  • Timers:
    • Non-retained: 192 (TON, TOF)
    • Retained: 64

I/O Specifications

  • Built-in I/O:
    • Digital Inputs: 36 (Sinking/Sourcing type, IEC type 1 sinking)
    • Digital Outputs: 24 (Relay, dry contact)
    • Analog I/O:
      • Process Image Size: 256-bit input (I), 256-bit output (Q)
      • Analog Input: 56 words (AI)
      • Analog Output: 56 words (AQ)

I/O Characteristics

Digital Inputs:

  • Allowable Continuous Voltage: Max. 30V DC
  • Surge Voltage (Max): 35V DC (lasting 0.5s)
  • Logic 1 Signal (Min): 15V DC with 2.5mA current
  • Logic 0 Signal (Max): 5V DC with 1mA current
  • Optical Isolation: 500V AC (lasting 1 minute)
  • Filter Time: Configurable per channel (ranging from 0.2 µs to 12.8 ms)

Digital Outputs (Relay, Dry Contact):

  • Voltage Range: 5V – 30V DC or 5V – 250V AC
  • Surge Current (Max): 7A when power is turned on
  • Rated Current per Point (Max): 2.0A
  • Switching Frequency: Not recommended for high-frequency switching
  • Turn-on Delay (Qa.0-Qa.3): Up to 10ms
  • Turn-off Delay (Qa.4-Qc.7): Up to 10ms
  • Optical Isolation: 500V AC (lasting 1 minute)
  • Contact Lifetime:
    • Non-loaded: 10 million cycles
    • Rated Load: 10,000 cycles

Expansion and Counters

  • Expansion Modules Allowed: Up to 6 modules
  • High-Speed Counters: 6 in total, with specific frequencies:
    • Single Phase: 4 counters at 200kHz + 2 counters at 30kHz
    • Quadrature Phase: 2 counters at 100kHz + 2 counters at 20kHz
  • Pulse Output: Not available

Communications and Ports

  • Ethernet:
    • 1 Ethernet port with 10/100 Mb/s data rate
    • CPU Communication (PUT/GET): 8 clients and 8 servers connections
    • Open Type Communication: 8 active and 8 passive connections
  • RS485:
    • 2 DB9-RS485 ports
    • 1 DB board serial port (CM01-RS485-RS232)
    • RS485 Free Port: Supports 1200 to 115200 b/s data transmission rates
  • HMI Connections:
    • 8 connections via Ethernet
    • 4 connections via serial port
  • Programming (PG) Connection: 1 connection

Performance and Processing Time

  • Boolean Operations: 0.35 µs per instruction
  • Moving Word Operations: 1.2 µs per instruction
  • Floating Point Operations: 1.7 µs per instruction