HUCEEN CPU SR30XP AC/DC/RLY

Description

E7 200Smart CPU Standard Edition,CPU SR30XP Relay,18DI/12DO/4AI/2AO,1*RJ45,2*RS485, Expandable to 6IO

General Overview

  • Model Number: SR30XP AC/DC/RLY
  • Article Number: E7 288-1SR30-XPA1
  • Description: Standard Edition CPU with 18 digital inputs, 12 digital outputs, 4 analog inputs, and 2 analog outputs, featuring relay-based digital outputs.
  • Dimensions (WxHxD): 125 mm × 100 mm × 81 mm
  • Power Consumption: 23W

Electrical Specifications

  • Available Current:
    • SM Bus: Max. 1400mA
    • 24V DC: Max. 300mA
  • Input Voltage: 85V – 264V DC
  • Input Current (CPU only):
    • Without 300mA sensor power supply: 130mA at 120V AC, 80mA at 240V AC
    • With 300mA sensor power supply: 250mA at 120V AC, 150mA at 240V AC
  • Input Current (Includes CPU + Expansion Modules):
    • At 120V AC: 300mA
    • At 240V AC: 190mA
  • Inrush Current (Max): 8.9A at 264V DC
  • Sensor Voltage: 20.4V – 28.8V DC
  • Isolation:
    • Input to Logic: 1500V AC (for 1 minute)
    • Sensor to Logic: Not isolated

Memory and Data

  • Program Memory: 18 KB
  • Data Memory: 12 KB
  • Retentive Memory: 10 KB (permanent data preservation)
  • Bit Memory (M): 256 bits
  • Cycle Interrupts: 2 (T32 and T96) with a 1ms resolution
  • Counters: 256
  • Timers:
    • Non-retained (TON, TOF): 192 timers
    • Retained: 64 timers

I/O Specifications

  • Built-in I/O:
    • Digital Inputs: 18 (Sinking/Sourcing type, IEC type 1 sinking)
    • Digital Outputs: 12 (Relay, dry contact)
    • Analog Inputs: 4 (Voltage/Current inputs)
    • Analog Outputs: 2 (Voltage/Current outputs)

Digital I/O Characteristics

Digital Inputs:

  • Allowable Continuous Voltage: Max. 30V DC
  • Surge Voltage (Max): 35V DC (lasting 0.5s)
  • Logic 1 Signal (Min): 15V DC at 2.5mA (standard inputs)
  • Logic 0 Signal (Max): 5V DC at 1mA
  • Optical Isolation: 500V AC (lasting 1 minute)
  • Filter Time: Configurable for each channel (ranging from 0.2 µs to 12.8 ms)

Digital Outputs (Relay, Dry Contact):

  • Voltage Range: 5V – 30V DC or 5V – 250V AC
  • Surge Current (Max): 7A (lasting 100ms)
  • Rated Current per Point (Max): 2.0A
  • Switching Frequency: Not recommended for high-frequency switching
  • Turn-on Delay (Qa.0 – Qa.3): Up to 10ms
  • Turn-off Delay (Qa.4 – Qb.3): Up to 10ms
  • Optical Isolation: 500V AC (lasting 1 minute)
  • Contact Lifetime:
    • Non-loaded: 10,000,000 cycles
    • Rated Load: 10,000 cycles

Analog I/O Characteristics

Analog Inputs (4 channels):

  • Input Types: Voltage or current (can be selected as a group)
  • Input Range:
    • Current Mode: 0-20mA
    • Voltage Mode: 0-10V
  • Resolution: 12 bits (both current and voltage modes)
  • Accuracy:
    • Voltage Mode: ±0.3% to ±0.5% of full scale range
    • Current Mode: ±0.4% to ±0.6% of full scale range
  • Analog-to-Digital Switching Time: 50ms (at 50Hz)

Analog Outputs (2 channels):

  • Output Types: Voltage or current
  • Output Range:
    • Current Mode: 0-20mA
    • Voltage Mode: 0-10V
  • Resolution: 11 bits (both current and voltage modes)
  • Accuracy:
    • Typical (at 25°C): ±0.5% to ±1.0% of full scale range
    • Worst Case (0 to 55°C): ±0.5% to ±1.0% of full scale range
  • Diagnosis: Upflow/underflow; 24V DC low voltage
  • Maximum Cable Length: 100m (Shielded twisted pair)

Performance and Processing Time

  • Boolean Operations: 0.35 µs per instruction
  • Moving Word Operations: 1.2 µs per instruction
  • Floating Point Operations: 1.7 µs per instruction

Communications and Ports

  • Ethernet:
    • 1 Ethernet port (10/100 Mb/s)
    • CPU Communication (PUT/GET): 8 clients and 8 servers connections
    • Open Type Communication: 8 active and 8 passive connections
  • RS485:
    • 2 DB9-RS485 ports
    • 1 DB board serial port (CM01-RS485-RS232)
    • RS485 Free Port: Supports 1200 to 115200 b/s data transmission rates
  • HMI Connections:
    • 8 connections via Ethernet
    • 4 connections via serial port
  • Programming (PG) Connection: 1 connection

Expansion and Counters

  • Expansion Modules Allowed: Up to 6 modules
  • High-Speed Counters: 6 in total, with specific frequencies:
    • Single Phase: 4 counters at 200kHz + 2 counters at 30kHz
    • Quadrature Phase: 2 counters at 100kHz + 2 counters at 20kHz
  • Pulse Output: None